(二)高压系统元件阻抗计算选择题
2-36(B)由
2-37(C)由
2-38(C)由
2-39(C)由
2-40(C)由
2-41(A)由
2-42(B)
2-43(A)由
2-44(C)由
(三)计算低压侧系统元件阻抗选择题
2-45(B)由
2-46(C)由XS=0.995ZS=0.8×0.995=0.796mΩ
2-47(A)由RS=0.1ZS=0.8×0.1=0.08mΩ
2-48(B)由
2-49(C)由
2-50(B)由
2-51(C)由
2-52(A)由
2-53(C)由RL=r0L=50×0.322=16.1mΩ
2-54(C)由XL=x0L=0.0733×50=3.665mΩ
2-55(A)由RL=r0L=0.0534×80=4.272mΩ
2-56(B)由XL=x0L=0.0264×80=2.112mΩ
(四)计算短路电流选择题
2-57(D)由
2-58(B)由
2-59(B) 由IK(2)=0.866IK=0.866×18.86
=16.33kA
2-60(C) 由 但
∴
2-61(B)由ip2=75KchIrM=7.5×1×2.1=15.8kA
则配电柜总冲击电流
ip=ip1+ip2=97.72+15.8=113.5kA
即配电柜允许冲击电流应大于113.5kA。
2-62(C)由iip2=75KchIrM=7.5×1.6×0.112
=1.344kA
则高压柜冲击电流:
ip=ip1+ip2=48.09+1.344=49.43kA
2-63(C)由
2-64(A) 应大于35.2kA.
2-65(C) 由
则动稳定允许冲击电流应大于89.25kA。
2-66(B)由
则开关柜的热稳定允许短路电流应大于38.33kA.
2-67(B)由灵敏系数K=IKmin/Izd3=25.33/24=1.06,
灵敏系数应K≥1.5故灵敏度不够。
2-68(C)由
即电缆截面应选用120mm2的电缆.
三.电气设备选择